Vulnerabilities (CVE)

Filtered by vendor Rockwellautomation Subscribe
Total 286 CVE
CVE Vendors Products Updated CVSS v2 CVSS v3
CVE-2020-14480 1 Rockwellautomation 1 Factorytalk View 2025-04-17 2.1 LOW 5.5 MEDIUM
Due to usernames/passwords being stored in plaintext in Random Access Memory (RAM), a local, authenticated attacker could gain access to certain credentials, including Windows Logon credentials.
CVE-2020-14478 1 Rockwellautomation 1 Factorytalk Services Platform 2025-04-17 5.6 MEDIUM 7.1 HIGH
A local, authenticated attacker could use an XML External Entity (XXE) attack to exploit weakly configured XML files to access local or remote content. A successful exploit could potentially cause a denial-of-service condition and allow the attacker to arbitrarily read any local file via system-level services.
CVE-2021-32960 1 Rockwellautomation 1 Factorytalk Services Platform 2025-04-17 6.0 MEDIUM 8.5 HIGH
Rockwell Automation FactoryTalk Services Platform v6.11 and earlier, if FactoryTalk Security is enabled and deployed contains a vulnerability that may allow a remote, authenticated attacker to bypass FactoryTalk Security policies based on the computer name. If successfully exploited, this may allow an attacker to have the same privileges as if they were logged on to the client machine.
CVE-2020-6998 1 Rockwellautomation 18 Armor Compact Guardlogix 5370, Armor Compact Guardlogix 5370 Firmware, Compact Guardlogix 5370 and 15 more 2025-04-17 N/A 5.8 MEDIUM
The connection establishment algorithm found in Rockwell Automation CompactLogix 5370 and ControlLogix 5570 versions 33 and prior does not sufficiently manage its control flow during execution, creating an infinite loop. This may allow an attacker to send specially crafted CIP packet requests to a controller, which may cause denial-of-service conditions in communications with other products.
CVE-2010-5305 1 Rockwellautomation 5 Plc5 1785-lx, Plc5 1785-lx Firmware, Rslogix and 2 more 2025-04-14 7.5 HIGH 9.8 CRITICAL
The potential exists for exposure of the product's password used to restrict unauthorized access to Rockwell PLC5/SLC5/0x/RSLogix 1785-Lx and 1747-L5x controllers. The potential exists for an unauthorized programming and configuration client to gain access to the product and allow changes to the product’s configuration or program. When applicable, upgrade product firmware to a version that includes enhanced security functionality compatible with Rockwell Automation's FactoryTalk Security services.
CVE-2024-11155 1 Rockwellautomation 1 Arena 2025-04-14 N/A 7.8 HIGH
A “use after free” code execution vulnerability exists in the Rockwell Automation Arena® that could allow a threat actor to craft a DOE file and force the software to use a resource that was already used. If exploited, a threat actor could leverage this vulnerability to execute arbitrary code. To exploit this vulnerability, a legitimate user must execute the malicious code crafted by the threat actor.
CVE-2015-6491 1 Rockwellautomation 2 Micrologix 1100 Firmware, Micrologix 1400 Firmware 2025-04-12 4.0 MEDIUM N/A
Allen-Bradley MicroLogix 1100 devices before B FRN 15.000 and 1400 devices before B FRN 15.003 allow remote authenticated users to insert the content of an arbitrary file into a FRAME element via unspecified vectors.
CVE-2016-2279 1 Rockwellautomation 46 Compactlogix 1756-en2f Series A, Compactlogix 1756-en2f Series A Firmware, Compactlogix 1756-en2f Series B and 43 more 2025-04-12 4.3 MEDIUM 6.1 MEDIUM
Cross-site scripting (XSS) vulnerability in the web server in Rockwell Automation Allen-Bradley CompactLogix 1769-L* before 28.011+ allows remote attackers to inject arbitrary web script or HTML via unspecified vectors.
CVE-2015-6486 1 Rockwellautomation 2 Micrologix 1100 Firmware, Micrologix 1400 Firmware 2025-04-12 6.5 MEDIUM N/A
SQL injection vulnerability on Allen-Bradley MicroLogix 1100 devices before B FRN 15.000 and 1400 devices before B FRN 15.003 allows remote authenticated users to execute arbitrary SQL commands via unspecified vectors.
CVE-2014-5424 1 Rockwellautomation 1 Connected Components Workbench 2025-04-12 7.5 HIGH N/A
Rockwell Automation Connected Components Workbench (CCW) before 7.00.00 allows remote attackers to cause a denial of service (application crash) or possibly execute arbitrary code via an invalid property value to an ActiveX control that was built with an outdated compiler.
CVE-2016-5645 1 Rockwellautomation 6 1766-l32awa, 1766-l32awaa, 1766-l32bwa and 3 more 2025-04-12 7.5 HIGH 7.3 HIGH
Rockwell Automation MicroLogix 1400 PLC 1766-L32BWA, 1766-L32AWA, 1766-L32BXB, 1766-L32BWAA, 1766-L32AWAA, and 1766-L32BXBA devices have a hardcoded SNMP community, which makes it easier for remote attackers to load arbitrary firmware updates by leveraging knowledge of this community.
CVE-2015-6492 1 Rockwellautomation 2 Micrologix 1100 Firmware, Micrologix 1400 Firmware 2025-04-12 7.8 HIGH N/A
Allen-Bradley MicroLogix 1100 devices before B FRN 15.000 and 1400 devices before B FRN 15.003 allow remote attackers to cause a denial of service (memory corruption and device crash) via a crafted HTTP request.
CVE-2014-9209 1 Rockwellautomation 2 Factorytalk Services Platform, Factorytalk View Studio 2025-04-12 6.9 MEDIUM N/A
Untrusted search path vulnerability in the Clean Utility application in Rockwell Automation FactoryTalk Services Platform before 2.71.00 and FactoryTalk View Studio 8.00.00 and earlier allows local users to gain privileges via a Trojan horse DLL in an unspecified directory.
CVE-2016-4531 1 Rockwellautomation 1 Factorytalk Energrymetrix 2025-04-12 7.5 HIGH 7.3 HIGH
Rockwell Automation FactoryTalk EnergyMetrix before 2.20.00 does not invalidate credentials upon a logout action, which makes it easier for remote attackers to obtain access by leveraging an unattended workstation.
CVE-2015-6488 1 Rockwellautomation 2 Micrologix 1100 Firmware, Micrologix 1400 Firmware 2025-04-12 4.3 MEDIUM N/A
Cross-site scripting (XSS) vulnerability in the web server on Allen-Bradley MicroLogix 1100 devices before B FRN 15.000 and 1400 devices before B FRN 15.003 allows remote attackers to inject arbitrary web script or HTML via unspecified vectors.
CVE-2016-4522 1 Rockwellautomation 1 Factorytalk Energrymetrix 2025-04-12 7.5 HIGH 9.8 CRITICAL
SQL injection vulnerability in Rockwell Automation FactoryTalk EnergyMetrix before 2.20.00 allows remote attackers to execute arbitrary SQL commands via unspecified vectors.
CVE-2015-6490 1 Rockwellautomation 2 Micrologix 1100 Firmware, Micrologix 1400 Firmware 2025-04-12 10.0 HIGH N/A
Stack-based buffer overflow on Allen-Bradley MicroLogix 1100 devices before B FRN 15.000 and 1400 devices through B FRN 15.003 allows remote attackers to execute arbitrary code via unspecified vectors.
CVE-2016-2277 1 Rockwellautomation 1 Integrated Architecture Builder 2025-04-12 6.9 MEDIUM 6.3 MEDIUM
IAB.exe in Rockwell Automation Integrated Architecture Builder (IAB) before 9.6.0.8 and 9.7.x before 9.7.0.2 allows remote attackers to execute arbitrary code via a crafted project file.
CVE-2014-9204 1 Rockwellautomation 1 Rslinx 2025-04-12 6.9 MEDIUM N/A
Stack-based buffer overflow in OPCTest.exe in Rockwell Automation RSLinx Classic before 3.73.00 allows remote attackers to execute arbitrary code via a crafted CSV file.
CVE-2016-5814 1 Rockwellautomation 5 Rslogix 500 Professional Edition, Rslogix 500 Standard Edition, Rslogix 500 Starter Edition and 2 more 2025-04-12 9.3 HIGH 8.6 HIGH
Buffer overflow in Rockwell Automation RSLogix Micro Starter Lite, RSLogix Micro Developer, RSLogix 500 Starter Edition, RSLogix 500 Standard Edition, and RSLogix 500 Professional Edition allows remote attackers to execute arbitrary code via a crafted RSS project file.