Vulnerabilities (CVE)

Filtered by vendor Schneider-electric Subscribe
Total 758 CVE
CVE Vendors Products Updated CVSS v2 CVSS v3
CVE-2011-4859 1 Schneider-electric 21 M340 Ethernet Module Bmxnoe0100, M340 Ethernet Module Bmxnoe0110, M340 Ethernet Module Bmxp342020 and 18 more 2025-04-11 10.0 HIGH N/A
The Schneider Electric Quantum Ethernet Module, as used in the Quantum 140NOE771* and 140CPU65* modules, the Premium TSXETY* and TSXP57* modules, the M340 BMXNOE01* and BMXP3420* modules, and the STB DIO STBNIC2212 and STBNIP2* modules, uses hardcoded passwords for the (1) AUTCSE, (2) AUT_CSE, (3) fdrusers, (4) ftpuser, (5) loader, (6) nic2212, (7) nimrohs2212, (8) nip2212, (9) noe77111_v500, (10) ntpupdate, (11) pcfactory, (12) sysdiag, (13) target, (14) test, (15) USER, and (16) webserver accounts, which makes it easier for remote attackers to obtain access via the (a) TELNET, (b) Windriver Debug, or (c) FTP port.
CVE-2013-2761 1 Schneider-electric 1 Modicon M340 2025-04-11 4.0 MEDIUM N/A
The Schneider Electric M340 BMXNOE01xx and BMXP3420xx PLC modules allow remote authenticated users to cause a denial of service (module crash) via crafted FTP traffic, as demonstrated by the FileZilla FTP client.
CVE-2013-0655 1 Schneider-electric 1 Software Update Utility 2025-04-11 9.3 HIGH N/A
The client in Schneider Electric Software Update (SESU) Utility 1.0.x and 1.1.x does not ensure that updates have a valid origin, which allows man-in-the-middle attackers to spoof updates, and consequently execute arbitrary code, by modifying the data stream on TCP port 80.
CVE-2012-0929 1 Schneider-electric 1 Modicon Quantum Plc 2025-04-11 7.8 HIGH 7.5 HIGH
Multiple buffer overflows in Schneider Electric Modicon Quantum PLC allow remote attackers to cause a denial of service via malformed requests to the (1) FTP server or (2) HTTP server.
CVE-2011-4034 1 Schneider-electric 3 Citecthistorian, Citectscada Reports, Vijeo Historian 2025-04-11 9.3 HIGH N/A
Buffer overflow in the Steema TeeChart ActiveX control, as used in Schneider Electric Vijeo Historian 4.30 and earlier, CitectHistorian 4.30 and earlier, and CitectSCADAReports 4.10 and earlier, allows remote attackers to execute arbitrary code or cause a denial of service via unspecified vectors.
CVE-2012-1990 1 Schneider-electric 2 Kerweb, Kerwin 2025-04-11 4.3 MEDIUM N/A
Multiple cross-site scripting (XSS) vulnerabilities in Schneider Electric Kerweb before 3.0.1 and Kerwin before 6.0.1 allow remote attackers to inject arbitrary web script or HTML via (1) the evtvariablename parameter in an evts.xml action to kw.dll, (2) unspecified search fields, or (3) unspecified content-display fields.
CVE-2011-4860 1 Schneider-electric 3 Quantum Ethernet Module 140noe77100, Quantum Ethernet Module 140noe77101, Quantum Ethernet Module 140noe77111 2025-04-11 10.0 HIGH N/A
The ComputePassword function in the Schneider Electric Quantum Ethernet Module on the NOE 771 device (aka the Quantum 140NOE771* module) generates the password for the fwupgrade account by performing a calculation on the MAC address, which makes it easier for remote attackers to obtain access via a (1) ARP request message or (2) Neighbor Solicitation message.
CVE-2013-2763 1 Schneider-electric 24 Modicon M340 Bmx Noc 0401, Modicon M340 Bmx Noc 0401 Firmware, Modicon M340 Bmx Noe 0100 and 21 more 2025-04-11 5.0 MEDIUM N/A
The Schneider Electric M340 PLC modules allow remote attackers to cause a denial of service (resource consumption) via unspecified vectors. NOTE: the vendor reportedly disputes this issue because it "could not be duplicated" and "an attacker could not remotely exploit this observed behavior to deny PLC control functions.
CVE-2013-6143 1 Schneider-electric 1 Telvent Sage 3030 Firmware 2025-04-11 5.0 MEDIUM N/A
The Schneider Electric Telvent SAGE 3030 RTU with firmware C3413-500-001D3_P4 and C3413-500-001F0_PB allows remote attackers to cause a denial of service (temporary outage and CPU consumption) via malformed DNP3 traffic.
CVE-2013-0663 1 Schneider-electric 3 Modicon M340, Modicon Premium, Modicon Quantum Plc 2025-04-11 6.8 MEDIUM N/A
Cross-site request forgery (CSRF) vulnerability on the Schneider Electric Quantum 140NOE77111, 140NOE77101, and 140NWM10000; M340 BMXNOC0401, BMXNOE0100x, and BMXNOE011xx; and Premium TSXETY4103, TSXETY5103, and TSXWMY100 PLC modules allows remote attackers to hijack the authentication of arbitrary users for requests that execute commands, as demonstrated by modifying HTTP credentials.
CVE-2013-2796 1 Schneider-electric 3 Citectscada, Powerlogic Scada, Vijeo Citect 2025-04-11 6.9 MEDIUM N/A
Schneider Electric Vijeo Citect 7.20 and earlier, CitectSCADA 7.20 and earlier, and PowerLogic SCADA 7.20 and earlier allow remote attackers to read arbitrary files, send HTTP requests to intranet servers, or cause a denial of service (CPU and memory consumption) via an XML document containing an external entity declaration in conjunction with an entity reference, related to an XML External Entity (XXE) issue.
CVE-2011-3143 2 Aveva, Schneider-electric 3 Clearscada, Scx 67, Scx 68 2025-04-11 10.0 HIGH N/A
Use-after-free vulnerability in Control Microsystems ClearSCADA 2005, 2007, and 2009 before R2.3 and R1.4, as used in SCX before 67 R4.5 and 68 R3.9, allows remote attackers to cause a denial of service (crash) and possibly execute arbitrary code via unspecified long strings that trigger heap memory corruption.
CVE-2011-4036 1 Schneider-electric 3 Citecthistorian, Citectscada Reports, Vijeo Historian 2025-04-11 5.0 MEDIUM N/A
Directory traversal vulnerability in Schneider Electric Vijeo Historian 4.30 and earlier, CitectHistorian 4.30 and earlier, and CitectSCADAReports 4.10 and earlier allows remote attackers to read arbitrary files via unspecified vectors.
CVE-2012-0931 1 Schneider-electric 1 Modicon Quantum Plc 2025-04-11 7.5 HIGH 9.8 CRITICAL
Schneider Electric Modicon Quantum PLC does not perform authentication between the Unity software and PLC, which allows remote attackers to cause a denial of service or possibly execute arbitrary code via unspecified vectors.
CVE-2011-3144 2 Aveva, Schneider-electric 3 Clearscada, Scx 67, Scx 68 2025-04-11 4.3 MEDIUM N/A
Cross-site scripting (XSS) vulnerability in Control Microsystems ClearSCADA 2005, 2007, and 2009 before R2.3 and R1.4, as used in SCX before 67 R4.5 and 68 R3.9, allows remote attackers to inject arbitrary web script or HTML via unspecified vectors.
CVE-2018-7841 1 Schneider-electric 1 U.motion Builder 2025-02-07 7.5 HIGH 9.8 CRITICAL
A SQL Injection (CWE-89) vulnerability exists in U.motion Builder software version 1.3.4 which could cause unwanted code execution when an improper set of characters is entered.
CVE-2023-25619 1 Schneider-electric 14 Bmeh58s, Bmeh58s Firmware, Bmep58s and 11 more 2025-02-05 N/A 7.5 HIGH
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists that could cause denial of service of the controller when communicating over the Modbus TCP protocol.
CVE-2023-6408 1 Schneider-electric 90 Ecostruxure Control Expert, Ecostruxure Process Expert, Modicon M340 Bmxp341000 and 87 more 2025-01-23 N/A 8.1 HIGH
CWE-924: Improper Enforcement of Message Integrity During Transmission in a Communication Channel vulnerability exists that could cause a denial of service and loss of confidentiality, integrity of controllers when conducting a Man in the Middle attack.
CVE-2023-6409 1 Schneider-electric 2 Ecostruxure Control Expert, Ecostruxure Process Expert 2024-12-11 N/A 7.7 HIGH
CWE-798: Use of Hard-coded Credentials vulnerability exists that could cause unauthorized access to a project file protected with application password when opening the file with EcoStruxure Control Expert.
CVE-2023-27975 1 Schneider-electric 2 Ecostruxure Control Expert, Ecostruxure Process Expert 2024-12-11 N/A 7.1 HIGH
CWE-522: Insufficiently Protected Credentials vulnerability exists that could cause unauthorized access to the project file in EcoStruxure Control Expert when a local user tampers with the memory of the engineering workstation.